Specialize in the Manufacture of Reliable Power Quality Products Since 2001

New generation ELC100-M intelligent combination low voltage reactive power measuring & control device

New generation ELC100-M intelligent combination low voltage reactive power measuring & control device

The ELC100-M is an integrated controller designed for reactive power compensation and power distribution monitoring. It combines data acquisition, communication, reactive power compensation, and grid parameter measurement and analysis into a single intelligent unit — controlled via a 4.3-inch HMI display with multi-language switching for better local user experience.

Two variants are available: ELC100-MZ, which uses RS485 communication to connect and control up to 32 EL-series combined low-voltage power capacitor compensation devices; and  ELC100 -MD, which uses 12V voltage output control mode, supporting up to 24 control outputs.

Built for reliable industrial operation, the controller works across an ambient temperature range of -25°C to +55°C, up to 2000m altitude, and handles rated voltage of 220V ±20% with THDv ≤5%. Measurement accuracy is tight — voltage ≤±0.5%, current ≤±0.5%, reactive power ≤±2%, and power factor ≤±1% — ensuring precise compensation control.

ELC100 is an integrated controller for reactive power compensation and power distribution monitoring. It integrates data acquisition, communication, reactive power compensation, grid parameter measurement, and analysis.

If this product adopts RS485 communication method (ELC100 -Z), it can connect up to 32 pieces of HY series combined low voltage power capacitor compensation device or select 12V voltage output Control method (ELC100 -D), which can provide 12 or 16 steps Output (only one of the two methods can be selected)

Model and Meaning

D1110100
|||||||||
34clock displaydata storageclock displaydata storageclock displaydata storagedata storage

1 with this function 0 without this function, can be customized

No.NameMeaning
1Control methodZ: RS485 communication D: 12V voltage output control
2Uplink communicationRS485 Modbus protocol-RTU)standard

*Note: ELC100 -D16 16 steps output(Can’t be configured with USB interface, capacitor current detection function)

Technical Parameters

Normal working and installation conditions
Ambient temperature-25°C ~ +55°C
Relative humidityRelative humidity ≤ 50% at 40°C ; ≤ 90% at 20°C
Altitude≤ 2000m
Environmental conditionsno harmful gas and steam, no conductive or explosive dust, no severe mechanical vibration

Power condition

Rated voltage220V±20%; THDv≤5%
Rated frequency50Hz ±5Hz
Performance 
Measurement accuracyVoltage: ≤ ±0.5%(0.8-1.2Un),current: ≤ ±0.5%(0.2-1.2ln), reactive power: ≤ ±2%, power factor: <±1%
Control quantityELC100-ZRs485 communication control 32 pieces of intelligent capacitors (mixed or three phase compensation) or 16 pieces of communication type composite switches
ELC100-D12V output control 12 steps or 16 steps (composite switch node)
Compensation methodmixed or three phase compensation
Control methodRS485
Protective functionOver-voltage protection, under-voltage protection, under-current protection, over-harmonic protection
StandardJB/T 9663-2013

Communication monitoring capability

Communication interfaceRS485
Communication protocolModbus protocol
Dimension and structureDimension(WxHxD)Mounting dimension(WxH)
 120*120*85113*113
ProductData SheetCatalog

New generation ELC100-M intelligent combination low voltage reactive power measuring & control device

DownloadDownload